How big a cable do I need?

Published in Cable Sizing 7 mins read

To determine how big a cable you need, you must consider several critical electrical factors, including the current the cable will carry, the acceptable voltage drop over its length, and the environmental conditions of its installation. Correct cable sizing is essential for safety, efficiency, and the optimal performance of your electrical systems.

Understanding Cable Sizing Fundamentals

Proper cable sizing prevents overheating, reduces energy loss, and ensures that electrical equipment receives adequate voltage. Overheating can lead to insulation damage, fire hazards, and equipment failure, while excessive voltage drop can cause motors to run inefficiently, lights to dim, and sensitive electronics to malfunction.

Understanding the fundamental electrical properties is crucial for proper cable selection. For example, to determine the target resistance required for a specific circuit, you can divide the voltage running through the cable by the target current. If your wire has a voltage of 150 Volts and your target current is 30 Amps, then dividing 150 by 30 gives you a target resistance of 5 Ohms. This understanding of circuit resistance is a foundational electrical concept. However, when selecting the physical size or gauge of a cable, practical applications primarily focus on its ability to safely carry current (ampacity) and minimize voltage drop over a given distance.

Key Factors Influencing Cable Size

Selecting the correct cable size involves a careful evaluation of the following factors:

1. Current (Ampacity)

The most critical factor is the maximum current (measured in Amperes or Amps) that the cable will carry. Ampacity is the maximum current a conductor can carry continuously under specific conditions without exceeding its temperature rating.

  • Calculate Total Current: Sum the current draw of all loads connected to the circuit. For continuous loads (operating for 3 hours or more), the National Electrical Code (NEC) often requires multiplying the load current by 125% for safety.
  • Consult Ampacity Tables: Electrical codes, such as the National Electrical Code (NEC) in the United States or BS 7671 in the UK, provide tables that list the maximum allowable ampacity for different wire gauges (AWG or mm²), conductor materials (copper or aluminum), and insulation types (e.g., THHN, XHHW).

Common Cable Sizes and Ampacities (Copper, 75°C Insulation)

The following table provides a general guide for copper conductors with 75°C insulation, which is common. Always refer to your local electrical codes for precise values and specific conditions.

AWG Size Approximate Diameter (mm) Typical Ampacity (Amps) Common Applications
14 AWG 1.63 15 Lighting, small appliances, general purpose outlets (15A circuits)
12 AWG 2.05 20 Kitchens, bathrooms, larger appliance circuits (20A circuits)
10 AWG 2.59 30 Water heaters, central heating, larger appliances
8 AWG 3.26 50 Electric ranges, sub-panels, high-demand equipment
6 AWG 4.11 65 HVAC units, large welders, main feeders for small sub-panels
4 AWG 5.19 85 Larger service feeders, industrial equipment
2 AWG 6.54 115 Main service feeders for medium-sized homes/buildings
1/0 AWG 7.35 150 Main service feeders for larger homes/small commercial

2. Voltage Drop

Voltage drop is the reduction in voltage along the length of a cable due to its resistance. Excessive voltage drop can lead to:

  • Reduced Performance: Motors may run hotter and less efficiently, lights may be dim.
  • Malfunctions: Sensitive electronic equipment may not operate correctly.
  • Increased Energy Consumption: Higher currents are drawn to compensate for lower voltage, leading to more heat and wasted energy.

Most electrical codes recommend keeping voltage drop to a maximum of 3% for feeder and branch circuits. For example, on a 120V circuit, a 3% drop is 3.6V (120V * 0.03 = 3.6V).

Voltage Drop Calculation Formula:

The formula for calculating voltage drop for a single-phase AC circuit (or DC) is:
$V_{drop} = \frac{(2 \times K \times I \times L)}{CM}$

Where:

  • $V_{drop}$ = Voltage Drop (Volts)

  • $K$ = Resistivity of the conductor material (12.9 for copper, 21.2 for aluminum, at 75°C)

  • $I$ = Current (Amps)

  • $L$ = Length of the cable (feet, one way)

  • $CM$ = Circular Mils of the conductor (refer to wire tables for this value)

  • Practical Insight: In many long-distance applications, voltage drop criteria will dictate a larger cable size than ampacity alone. Always calculate both and select the larger wire size.

3. Cable Length

The longer the cable, the greater its total resistance, and thus the higher the voltage drop for a given current. This is why length is a critical input for voltage drop calculations. For short runs, ampacity is usually the primary concern; for longer runs, voltage drop often becomes the dominant factor in determining cable size.

4. Environmental Conditions & Installation Method

  • Ambient Temperature: Higher ambient temperatures reduce a cable's ampacity because the cable cannot dissipate heat as effectively. You may need to derate (reduce) the cable's current-carrying capacity or select a larger gauge.
  • Cable Grouping: When multiple current-carrying cables are bundled together or enclosed in a conduit, their ability to dissipate heat is reduced. This also requires derating, meaning you'll need a larger wire size for the same current.
  • Insulation Type: Different insulation materials have different temperature ratings. Cables rated for higher temperatures (e.g., 90°C) can generally carry more current than those rated for lower temperatures (e.g., 60°C or 75°C) for the same gauge, assuming terminals are rated for the higher temperature.
  • Installation Method: Cables installed in open air dissipate heat more easily than those in conduit, direct buried, or in thermal insulation.

Step-by-Step Cable Sizing Process

  1. Determine the Load Current:
    • Identify all connected loads (appliances, lights, motors).
    • Calculate the total amperage draw. Remember to account for continuous loads (125%).
  2. Determine the Circuit Voltage:
    • Is it 120V, 240V, 208V, or another voltage?
  3. Measure the Cable Length:
    • Measure the one-way distance from the power source to the load.
  4. Establish Voltage Drop Limits:
    • Typically 3% for feeders and branch circuits as per local codes.
  5. Consult Ampacity Tables:
    • Based on your calculated load current, refer to relevant ampacity tables in your local electrical code for your conductor material (copper or aluminum) and insulation type. This will give you a minimum wire size based purely on current.
  6. Calculate Voltage Drop for the Ampacity-Sized Cable:
    • Using the voltage drop formula, calculate the voltage drop for the wire size determined in step 5, over your measured length, and with your calculated current.
    • If the calculated voltage drop exceeds your allowed limit (e.g., 3%), you must select a larger wire size.
  7. Apply Derating Factors (if necessary):
    • If the ambient temperature is high or if multiple cables are grouped, apply the appropriate derating factors from your electrical code. This will further reduce the effective ampacity of the chosen wire, potentially requiring an even larger size.
  8. Select the Final Cable Size:
    • Choose the larger of the two sizes determined by ampacity requirements (after derating) and voltage drop calculations. Always err on the side of caution and use a slightly larger wire if unsure.

Practical Considerations and Safety

  • Always Refer to Local Codes: The information provided here is general. Always consult your local electrical codes (e.g., NFPA 70: National Electrical Code (NEC) in the U.S., IET Wiring Regulations (BS 7671) in the UK, or similar standards globally) for specific requirements in your region. These codes are law and are designed for safety.
  • Oversize if in Doubt: If you are between two sizes or have any uncertainty, choosing the next larger wire size is always safer and can improve efficiency.
  • Professional Help: For complex electrical installations or if you are unsure, always consult a qualified and licensed electrician. They have the expertise and tools to ensure your wiring is safe and compliant.